Due to the current geopolitical situation in parts of the Middle East, we have restricted public access to addresses and coordinates in select countries. During this period, detailed location data will only be available to subscribing clients.
d-Site Scan: Computerized Building Management System M&E equipment verification and management
ELECTRICAL SYSTEM ------------------------- a-Design Load: The electrical connected load is 1.2 MVA with a demand load of 0.9 MVA.
b-Transformer: 2 x 1500 kVA Power Transformer, 380/220V, 3P, 4W, 60Hz.
c-Generator: 3 x 2354 kVA/1883 kW Continuous Rated Generator configured in N+1.
d-Paralleling Switch gear: One set of paralleling switch gear for concurrently maintainable requirements which is controlled and monitored by Load Shedding Panel.
c-UPS: Parallel redundant system in N+1 configuration, 200KVA modular units with 30 minute battery autonomy at full load. 1000 W/m2 for Data Center.
d-Rectifier System: Active + Active System, (N+N) at 200 W/m2, 1000 Ah for 2 hrs + 2hrs battery autonomy time.
e-Security System: IP access control system and Analog CCTV system
Pricing & Services
If you are looking for colocation, cloud, connectivity or other services in Mobily Maddinah, other data centers in Maddinah or operated by Mobily, please try our free quote service or reach out for a free consultation about your data center needs. We use a best effort process to qualify opportunities and route them to matching operators.
Advertisement
Mobily
Data Center Operator at Mobily Maddinah Headquartered in Riyadh, Saudi Arabia